Research

A New Digital Relay for Generator Protection against Asymmetrical Faults


Reference:

Usta, O., Bayrak, M. and Redfern, M. A., 2001. A New Digital Relay for Generator Protection against Asymmetrical Faults. Power Engineering Review, IEEE, 21 (11), p. 58.

Related documents:

This repository does not currently have the full-text of this item.
You may be able to access a copy if URLs are provided below.

Abstract

Under unbalanced conditions the three phase instantaneous power oscillates at twice the power system frequency. The magnitude of these oscillations can be used as a measure of the system unbalance. This article has introduced a new digital relaying algorithm designed to detect asymmetrical faults by monitoring the sinusoidal oscillations of the three phase instantaneous power measured at the generator terminal. Once an asymmetrical fault is detected, the algorithm checks the direction of the negative sequence-reactive power flow at the machine terminal to discriminate between internal and external faults. Power system test studies presented show that the new relay provides fast tripping for internal asymmetrical faults and back-up protection for external asymmetrical fault conditions.

Details

Item Type Articles
CreatorsUsta, O., Bayrak, M. and Redfern, M. A.
Uncontrolled Keywordsunbalanced power component, digital relaying, asymmetrical faults, generator protection
DepartmentsFaculty of Engineering & Design > Electronic & Electrical Engineering
RefereedYes
StatusPublished
ID Code6118

Export

Actions (login required)

View Item