Research

Detecting loss of earth for embedded generation


Reference:

Redfern, M. A., Brown, D. and Bartlett, M. G., 2001. Detecting loss of earth for embedded generation. In: Seventh International Conference on Developments in Power System Protection, 2001 (IEE), 2001-04-09 - 2001-04-12, Amsterdam.

Related documents:

This repository does not currently have the full-text of this item.
You may be able to access a copy if URLs are provided below.

Official URL:

http://dx.doi.org/10.1049/cp:20010107

Abstract

This paper describes research into new techniques for automatically detecting loss of earth for an embedded generator. The techniques investigated take advantage of the parasitic impedances associated with a practical generator. These are used to determine whether or not the system to which the embedded generator is connected is earthed. The protection algorithms are designed to use well established techniques and to provide high speed tripping. The principles of operation are such that they can be developed for a multi-function microprocessor based relay or used in a stand alone relay. The paper includes details of practical tests conducted on a LV embedded generator system to demonstrate the principles involved

Details

Item Type Conference or Workshop Items (Paper)
CreatorsRedfern, M. A., Brown, D. and Bartlett, M. G.
DOI10.1049/cp:20010107
Uncontrolled Keywordsparasitic impedances, relay protection, multi-function microprocessor based relay, stand alone relay, power system protection, power engineering computing, operation principles, loss of earth detection, microcomputer applications, high speed tripping, embedded generation, protection algorithms, electric power generation, earthing, distribution networks, lv embedded generator system, electric impedance
DepartmentsFaculty of Engineering & Design > Electronic & Electrical Engineering
RefereedNo
StatusPublished
ID Code6138

Export

Actions (login required)

View Item